Night cooled radiant cooling panel for sustainable building cooling mode in Malaysia

Baharun, A; Imran, M S; Ibrahim, S H and Abidin, W A W Z (2018) Night cooled radiant cooling panel for sustainable building cooling mode in Malaysia. Journal of Construction in Developing Countries, 23(1), pp. 61-79. ISSN 1823-6499

Abstract

Night air temperature in Malaysia is generally about 23°C and is a potential source of heat sink to dissipate heat gain from a building. A thermal storage tank was used to store a certain quantity of water and was passively cooled during the night using the pitched roof as a heat exchanger to chill the water to as low as 22°C. The free cooling of water was then used as a cooling medium to cool the modular radiant cooling panel during the day time when the outdoor temperature exceeds 30°C. The experiment shows that the system was able to maintain an indoor temperature of less than 28°C when the outdoor temperature peaked to nearly 34°C while providing acceptable thermal comfort with certain controlled air movement. The use of the hydronic radiant cooling panel with free night cooled water as its coolant is proven to have significant energy saving potential of up to 85% while at the same time provide an acceptable room thermal comfort which meets the international standard criteria such as the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Standard 55.

Item Type: Article
Uncontrolled Keywords: energy conservation; night cooled water; night sky cooling; passive system; thermal comfort
Index terms: energy-saving, air movement, Malaysia, night cooled water, sustainable building, energy conservation, thermal comfort, air temperature, pitched roof, indoor temperature, passive system, engineer, society, night sky cooling, experiment
Subjects: energy systems, architectural elements, environmental science, Geography, profession, environmental engineering, data collection methods, communities and social development, sustainable construction, energy efficiency
Topics: Sustainability, Research Practice, Roles and Professions, Design Practice, Stakeholder Management, Geographical Context
Descriptive scope: 3 PCE

N.B. Descriptive scope is a count of how many of the five facets of empirical research are indicated by the words used in title, abstract and keywords. It is not intended as a judgement on the research; merely a count of the kind of word we would expect to indicate Phenomenon, Concepts, Theoretical framing, Empirical techniques, Analytical techniques. If all five are present, then a code of “5 PCTEA” will indicate this. If you feel the coding for this record is questionable, we welcome discussion around the terms we matched or the way we categorized them. The facet you would expect may not be coded, or a facet may be coded inappropriately. This can also bear on a larger question, of which facets should be treated as defining in construction management research. Please get in touch, and we will look at it. More details here