Qi, J K; Yang, J Y; Oliver Hoon Leh, L; Edwards, R and Jamalunlaili, A (2021) Thermal comfort prediction of air-conditioned and passively cooled engineering testing centres in a higher educational institution using CFD. Smart and Sustainable Built Environment, 10(1), pp. 18-36. ISSN 2046-6099
Abstract
The purpose of this paper is to analyse the thermal environment of two engineering testing centres cooled via different means using computational fluid dynamics (CFD), focussing on the indoor temperature and air movement. This computational technique has been used in the analysis of thermal environment in buildings where the profiles of thermal comfort parameters, such as air temperature and velocity, are studied. A pilot survey was conducted at two engineering testing centres – a passively cooled workshop and an air-conditioned laboratory. Electronic sensors were used in addition to building design documentation to collect the required information for the CFD model–based prediction of air temperature and velocity distribution patterns for the laboratory and workshop. In the models, both laboratory and workshop were presumed to be fully occupied. The predictions were then compared to empirical data that were obtained from field measurements. Operative temperature and predicted mean vote (PMV)–predicted percentage dissatisfied (PPD) indices were calculated in each case in order to predict thermal comfort levels. The simulated results indicated that the mean air temperatures of 21.5°C and 32.4°C in the laboratory and workshop, respectively, were in excess of the recommended thermal comfort ranges specified in MS1525, a local energy efficiency guideline for non-residential buildings. However, air velocities above 0.3 m/s were predicted in the two testing facilities, which would be acceptable to most occupants. Based on the calculated PMV derived from the CFD predictions, the thermal sensation of users of the air-conditioned laboratory was predicted as −1.7 where a “slightly cool” thermal experience would prevail, but machinery operators in the workshop would find their thermal environment too warm with an overall sensation score of 2.4. A comparison of the simulated and empirical results showed that the air temperatures were in good agreement with a percentage of difference below 2%. However, the level of correlation was not replicated for the air velocity results, owing to uncertainties in the selected boundary conditions, which was due to limitations in the measuring instrumentation used. Due to the varying designs, the simulated results of this study are only applicable to laboratory and workshop facilities located in the tropics The results of this study will enable building services and air-conditioning engineers, especially those who are in charge of the air-conditioning and mechanical ventilation (ACMV) system design and maintenance to have a better understanding of the thermal environment and comfort conditions in the testing facilities, leading to a more effective technical and managerial planning for an optimised thermal comfort management. The method of this work can be extended to the development of CFD models for other testing facilities in educational institutions. The findings of this work are particularly useful for both industry and academia as the indoor environment of real engineering testing facilities were simulated and analysed. Students and staff in the higher educational institutions would benefit from the improved thermal comfort conditions in these facilities For the time being. CFD studies have been carried out to evaluate thermal comfort conditions in various building spaces. However, the information of thermal comfort in the engineering testing centres, of particular those in the hot–humid region are scantily available. The outcomes of this simulation work showed the usefulness of CFD in assisting the management of such facilities not only in the design of efficient ACMV systems but also in enhancing indoor thermal comfort.
| Item Type: | Article |
|---|---|
| Uncontrolled Keywords: | thermal comfort; computational fluid dynamics; higher educational institutions; ventilation; nonresidential buildings; workshops; residential areas; instrumentation; indoor environments; building services; mathematical models; simulation |
| Index terms: | residential area, workshop, thermal environment, non-residential building, comfort, testing, ventilation, indoor temperature, academia, instrumentation, velocity distribution, energy efficiency, sensation, engineer, computational fluid dynamics, indoor environment, operative, building design, air temperature, air movement, thermal comfort, field-measurement, boundary condition, mathematical model, mechanical ventilation, documentation, building service, laboratory, survey, thermal sensation |
| Subjects: | engineering systems, professional practice, air quality, human factors and perception, analytical methods, construction type, research management, environmental science, environmental engineering, zoning, practitioner, mathematical modelling, modelling and simulation, educational institutions, occupational health and safety management, professional development, data collection methods, sustainability and energy, fluid mechanics, structural engineering, architectural design, profession |
| Topics: | Engineering Principles, Urban Studies, Sustainability, Construction Technology, Research Practice, Health and Safety, Design Practice, Digital Applications, Roles and Professions, Education, Information Management |
| Descriptive scope: | 4 PCEA |
N.B. Descriptive scope is a count of how many of the five facets of empirical research are indicated by the words used in title, abstract and keywords. It is not intended as a judgement on the research; merely a count of the kind of word we would expect to indicate Phenomenon, Concepts, Theoretical framing, Empirical techniques, Analytical techniques. If all five are present, then a code of “5 PCTEA” will indicate this. If you feel the coding for this record is questionable, we welcome discussion around the terms we matched or the way we categorized them. The facet you would expect may not be coded, or a facet may be coded inappropriately. This can also bear on a larger question, of which facets should be treated as defining in construction management research. Please get in touch, and we will look at it. More details here