Ogden, R G; Kendrick, C C and Walliman, N S R (2004) Modelling of enhanced passive and conventional cooling systems. Building Research & Information, 32(1), pp. 17-26. ISSN 0961-3218
Abstract
This study modelled a recently completed typical steel-framed speculative office development in the UK. It investigated the comparative performance of the building for various servicing regimes. These included natural and mechanical ventilation, two types of active fabric energy storage (FES) system (AirDeck and AirCore), air-conditioning (a conventional all-air system and chilled ceiling with mechanical ventilation), and mixed-mode solutions combining some of the above approaches. The assessment covered both summer and winter (heating) performance. The main objective was to evaluate overall performance of these systems in terms of thermal comfort and energy use and to compare the findings with more conventional servicing options for the same building. The study demonstrates that active FES can enhance thermal comfort while reducing energy use and emissions. In comparison with conventionally and naturally ventilated systems, the studied FES systems reduced temperature excess hours and peak temperatures, supplied cooler air as a result of overnight cooling, and reduced chiller consumption and boiler ratings as well as emissions. The annual operating costs of these active FES systems increase energy costs by only 13% over that of the naturally ventilated option. The mixed-mode solutions reduce them by over 35% when compared with ail-mechanically cooled alternatives.
| Item Type: | Article |
|---|---|
| Uncontrolled Keywords: | air-conditioning; conventional cooling; dynamic thermal simulation; fabric energy storage; mechanical ventilation; natural ventilation; office buildings; steel-framed buildings |
| Index terms: | cooling system, consumption, office building, option, energy storage, modelling, mechanical ventilation, natural ventilation, thermal comfort, operating cost, winter, energy use, servicing, energy cost, summer |
| Subjects: | maintenance engineering, energy systems, decision analysis, environmental engineering, climate science, analytical methods, construction type, mechanical systems, consumer economics, cost management, economic analysis |
| Topics: | Stakeholder Management, Sustainability, Risk Management, Engineering Principles, Construction Technology, Business Strategy |
| Descriptive scope: | 2 PC |
N.B. Descriptive scope is a count of how many of the five facets of empirical research are indicated by the words used in title, abstract and keywords. It is not intended as a judgement on the research; merely a count of the kind of word we would expect to indicate Phenomenon, Concepts, Theoretical framing, Empirical techniques, Analytical techniques. If all five are present, then a code of “5 PCTEA” will indicate this. If you feel the coding for this record is questionable, we welcome discussion around the terms we matched or the way we categorized them. The facet you would expect may not be coded, or a facet may be coded inappropriately. This can also bear on a larger question, of which facets should be treated as defining in construction management research. Please get in touch, and we will look at it. More details here