Ji, Y; Lee, A and Fernando, T (2020) Dynamic thermal simulation of advanced natural ventilation in buildings: Current and future usage, UK exemplar. Architectural Engineering and Design Management, 16(4), pp. 293-309. ISSN 1745-2007
Abstract
This paper evaluates the use of advanced natural ventilation (ANV) strategies in a range of climatic conditions from four cities in the UK. A prototype ANV system was proposed to determine the most effective case in mitigating overheating. The case was then assessed under identical simulation conditions for all four ANV strategies. The overheating criteria used in the research include the single temperature criterion from CIBSE Guide A and the adaptive thermal comfort overheating criteria from BS EN 15251. Both the current and future 'Design Summer Year (DSY)' weather data were used to examine the thermal performances of the proposed design. The findings show that shading, night cooling and heavy weight structures (ceiling) were all useful in mitigating overheating, with night cooling being identified as the most effective measure. The work assessed the use of ANV in both current and future scenarios to quantify the limits of outdoor environmental conditions under which natural ventilation is an effective strategy for achieving thermal comfort. The adaptive thermal comfort overheating criteria were proved to be easier to meet compared with the CIBSE single temperature criterion. With the adaptive overheating criteria, the given design is predicted to not overheat until 2050 in London Heathrow; and for other places evaluated in the UK (Edinburgh, Manchester & Birmingham), the design passes these criteria. The Centre-in ANV strategies proved to be more effective than the Edge-in strategies for space cooling due to the extended structure thermal mass.
| Item Type: | Article |
|---|---|
| Uncontrolled Keywords: | adaptive thermal comfort; advanced natural ventilation; design summer year; dynamic thermal simulation; overheating |
| Index terms: | shading, weather, environmental conditions, London, thermal performance, natural ventilation, summer, thermal comfort, overheating, strategy, prototype, Birmingham, climatic condition |
| Subjects: | modelling and simulation, environmental science, energy systems, air quality, climate science, thermal systems, environmental engineering, management, building design, Geography |
| Topics: | Design Practice, Sustainability, Business Strategy, Engineering Principles, Geographical Context |
| Descriptive scope: | 2 PC |
N.B. Descriptive scope is a count of how many of the five facets of empirical research are indicated by the words used in title, abstract and keywords. It is not intended as a judgement on the research; merely a count of the kind of word we would expect to indicate Phenomenon, Concepts, Theoretical framing, Empirical techniques, Analytical techniques. If all five are present, then a code of “5 PCTEA” will indicate this. If you feel the coding for this record is questionable, we welcome discussion around the terms we matched or the way we categorized them. The facet you would expect may not be coded, or a facet may be coded inappropriately. This can also bear on a larger question, of which facets should be treated as defining in construction management research. Please get in touch, and we will look at it. More details here